§ 15.03.040. AMENDMENTS TO THE CALIFORNIA RESIDENTIAL CODE.  


Latest version.
  • The 2019 Edition of the California Residential Code is amended as set forth in this section:
    .010 The Anaheim Residential Code is hereby amended, modified and supplemented by the addition and application of the provisions of Section 15.03.040 of this Code.
    .020 Table R301.2(1) of Chapter 3 is revised to read in full as follows:
    MANUAL J DESIGN CRITERIA n
    MANUAL J DESIGN CRITERIA (n)
    ELEVATION
    LATITUDE
    WINTER HEATING
    SUMMER COOLING
    ALTITUDE CORRECTION FACTOR
    INDOOR DESIGN TEMPERATURE
    DESIGN TEMPERATURE COOLING
    HEAT TEMPERATURE DIFFERENCE
    305
    34
    37
    91
    70
    75
    COOLING TEMPERATURE DIFFERENCE
    WIND VELOCITY HEATING
    WIND VELOCITY COOLING
    COINCIDENT WET BULB
    DAILY RANGE
    WINDER HUMIDITY
    SUMMER HUMIDITY
    7
    69
    27
    7 (50% RH)
    For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour = 0.447 m/s.
    a. Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements of this code. The weathering column shall be filled in with the weathering index (i.e., "negligible," "moderate" or "severe") for concrete as determined from the Weathering Probability Map [Figure R301.2(3)]. The grade of masonry units shall be determined from ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C 652.
    b. The frost line depth may require deeper footings than indicated in Figure R403.1(1). The jurisdiction shall fill in the frost line depth column with the minimum depth of footing below finish grade
    c. The jurisdiction shall fill in this part of the table to indicate the need for protection depending on whether there has been a history of local subterranean termite damage.
    d. The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [Figure R30l.2( 4)].Wind exposure category shall be determined on a site-specific basis in accordance with Section R301.2.1.4.
    e. The outdoor design dry-bulb temperature shall be selected from the columns of 971/2-percent values for winter from Appendix D of the California Plumbing Code. Deviations from the Appendix D temperatures shall be permitted to reflect local climates or local weather experience as determined by the building official.
    f. The jurisdiction shall fill in this part of the table with the seismic design category determined from Section R301.2.2.1.
    g. Please see the City's Website for Flood Hazard Zones Maps.
    h. In accordance with Sections R905.2.7.1, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and R905.8.3.1, where there has been a history of local damage from the effects of ice damming, the jurisdiction shall fill in this part of the table with "YES." Otherwise, the jurisdiction shall fill in this part of the table with "NO."
    i. The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (BF-days) from Figure R403.3(2) or from the l00-year (99%) value on the National Climatic Data Center data table "Air Freezing Index- USA Method (Base 32°)" at www.ncdc.noaa.gov/fpsf.html.
    j. The jurisdiction shall fill in this part of the table with the mean annual temperature from the National Climatic Data Center data table "Air Freezing Index-USA Method (Base 32°F)" at www.ncdc.noaa.gov/fpsf.html.
    k. In accordance with Section R301.2.1.5, where there is local historical data documenting structural damage to buildings due to topographic wind speed-up effects, the jurisdiction shall fill in this part of the table with "YES." Otherwise, the jurisdiction shall indicate "NO" in this part of the table.
    l. In accordance with Figure R301.2(4)A, where there is local historical data documenting unusual wind conditions, the jurisdiction shall fill in this part of the table with "YES" and identify any specific requirements. Otherwise, the jurisdiction shall indicate "NO" in this part of the table.
    m. In accordance with Section R301.2.1.2.1, the jurisdiction shall indicate the wind-borne debris wind zone(s). Otherwise, the jurisdiction shall indicate "NO" in this part of the table.
    n. The jurisdiction shall use the design criteria in Table 1a or 1b from ACCA Manual J or established criteria determined by the Authority Having Jurisdiction.
    .030 Subsection R902.1 of Section R902 of Chapter 9 is revised to allow only class A or B roofs as follows:
    R902.1 Roofing covering materials. Roofs shall be covered with materials as set forth in Sections R904 and R905. A minimum Class A or B roofing shall be installed in areas designated by this section. Classes A or B roofing required by this section to be listed shall be tested in accordance with UL 790 or ASTM E 108.
    Exceptions:
    1. Class A roof assemblies include those with coverings of brick, masonry and exposed concrete roof deck.
    2. Class A roof assemblies also include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile, or slate installed on noncombustible decks.
    .040 Paragraph R902.1.3 of Subsection R902.1 of Section R902 of Chapter 9 is revised it to require a minimum Class B roof as follows:
    R902.1.3 Roof coverings within all other areas. The entire roof covering of every existing structure where more than 50 percent of the total roof area is replaced within any one-year period, the entire roof covering of every new structure, and any roof covering applied in the alteration, repair or replacement of the roof of every existing structure, shall be a fire-retardant roof covering that is at least Class B.
    .050 The first paragraph of Subsection R902.2 of Section R902 of Chapter 9 is revised to allow only Class A or B treated wood roofs as follows:
    R902.2 Fire-retardant-treated shingles and shakes. Fire-retardant-treated wood shakes and shingles are wood shakes and shingles complying with UBC Standard 15-3 or 15-4 which are impregnated by the full-cell vacuum-pressure process with fire-retardant chemicals, and which have been qualified by UBC Standard 15-2 for use on Class A or B roofs.
    .060 Subsection AV100.2(a) of Section AV100.2 of Appendix V is hereby amended as follows:
    Except as provided in Section AV100.5, when a building permit is issued for the construction of a new swimming pool or spa or the remodeling of an existing swimming pool or spa at a private single-family home, the respective swimming pool or spa shall be equipped with item #1 below AND at least one additional following seven drowning prevention features.
    .070 Paragraph AV100.2(a)(1) of Subsection AV100.2(a) of Appendix V is amended as follows:
    1. An enclosure that meets the requirements of AV100.3 and isolates the swimming pool and spa from the private single-family home. Any walls of the residential structure or accessory structures used to complete the isolation enclosure must have door openings equipped with protection as required in AV100.2 (a) #4 or #5. Any such door protection device provided for this purpose may not be used to comply with the second drowning prevention feature requirement.
    (Ord. 6477, §2 (part); February 4, 2020.)